allinpue.com / Guides / What is PUE
Guide · Definition

What is PUE? The formula, a worked example and the traps

Power usage effectiveness divides a data center's total energy by the energy its IT equipment uses over a year. It is simple to define and easy to misread. This guide shows the formula, a full worked example and the five ways a PUE figure misleads.

Updated October 20267 min readBy Ziya DemirData center project directorFounder of allindatacenter.com

In short

  • PUE = total facility energy ÷ IT equipment energy, both in kWh over the same 12 months.
  • 1.0 is the theoretical floor. Everything above it is overhead: cooling, power losses, lighting.
  • The global average is about 1.54 (Uptime Institute, 2025); hyperscale fleets report 1.09 to 1.15.
  • Defined by The Green Grid in 2007, standardised as ISO/IEC 30134-2 in 2016.
  • Germany now requires 1.2 for new data centers; the EU collects PUE from every site of 500 kW IT or more.
01 · Formula

The formula

ISO/IEC 30134-2
PUE = Total facility energyIT equipment energy
Both values in kWh over the same 12 months. A one-off kW reading is a snapshot, not a PUE.

A PUE of 1.30 means that for every 100 kWh delivered to servers, storage and network, the building uses another 30 kWh to cool them, convert power and keep the lights on.

The inverse, DCiE (data center infrastructure efficiency), expresses the same thing as a percentage: DCiE = 1 ÷ PUE × 100 %. A PUE of 1.25 is a DCiE of 80 %. The industry has largely dropped DCiE, but older reports still use it.

02 · Example

A worked example: 2 MW of IT at 70 % load

A hall with 2 MW of installed IT, running at an average 70 % over the year, uses 2 MW × 0.70 × 8,760 h = 12,264 MWh of IT energy. The meters on the cooling plant, the power chain and the building add the rest:

Energy use over 12 monthsMWhShare of IT
IT equipment (servers, storage, network)12,264100 %
Cooling (chillers, CRAH fans, pumps, towers)2,45320 %
Power chain losses (UPS, transformers, PDUs)9818 %
Lighting, security, building services2452 %
Total facility energy15,943PUE 1.30

Cut cooling from 20 % to 12 % of IT energy, for example with containment and free cooling, and the total falls by 981 MWh to 14,962 MWh: PUE 1.22. At $120 per MWh that is about $118,000 a year on a single 2 MW hall.

Try it with your own numbersThe allinPUE calculator converts every tenth of PUE into energy, cost and CO₂ for any grid.
Open the calculator →
03 · Boundary

What counts as IT, and what counts as facility

IT equipment energyFacility overhead
Servers, including their internal fansChillers, cooling towers, dry coolers, pumps
Storage arrays and backup systemsCRAH / CRAC units and fan walls
Network switches, routers, firewallsUPS, transformer and distribution losses
Monitoring and management equipment in the racksLighting, security, fire systems, BMS

Where the IT energy is metered matters as much as what is metered. That is what the measurement categories describe.

04 · Categories

Measurement categories 0 to 3

CategoryBasisIT energy measured atUse
Cat 0Peak demand (kW)UPS outputEntry level, no longer recommended
Cat 1Annual energyUPS outputCommon minimum
Cat 2Annual energyPDU outputBetter: excludes PDU losses from IT
Cat 3Annual energyServer inputMost accurate

Always state the category with the number. A Category 1 PUE counts PDU losses as IT energy and so looks better than the same site measured at Category 3.

05 · Traps

Five ways a PUE figure misleads

1. Low utilisation inflates it

Cooling and electrical overheads have a fixed share. A new hall at 30 % load can show a PUE far above its design value. Compare sites at the same load point.

2. Climate sets the floor

Free-cooling hours vary by site. A Nordic campus gets far more economiser hours than the same design in Singapore or the Gulf.

3. A lower PUE can hide higher IT energy

Raising supply-air temperature cuts chiller energy but can raise server fan power, which counts as IT. Check total facility energy, not PUE alone.

4. Partial PUE is not PUE

A pPUE for one hall or one subsystem leaves out shared plant. Ask which boundary a quoted figure uses.

5. Design PUE is not annual PUE

Design PUE is usually calculated at full load on a design day. Annual PUE at real load is what regulators and lenders look at. Singapore quotes full load, Germany an annual average.

06 · Related

PUE and its sister metrics

MetricMeasuresUnit
WUEWater usage effectivenesslitres per kWh IT
CUECarbon usage effectivenesskg CO₂ per kWh IT
ERFEnergy reuse factorreused ÷ total energy
REFRenewable energy factorrenewable ÷ total energy

EU data centers of 500 kW IT or more now report all four alongside PUE. Heat reuse does not lower PUE; it shows up in ERF. See allinHEATREUSE for the heat side.

07 · Questions

Questions about PUE

What is a good PUE?

For a new build in a temperate climate, 1.2 to 1.3 as an annual average is good and 1.2 is now the legal limit for new sites in Germany. Hyperscale fleets report 1.09 to 1.15. The global average is about 1.54.

Can PUE be below 1.0?

No. Total facility energy always includes the IT energy, so the ratio cannot fall below 1.0. Exporting waste heat does not change PUE; it is measured with ERF.

Is a lower PUE always better?

Not on its own. A site can lower PUE by shifting energy into the IT side, for example hotter air that makes server fans work harder. Look at total energy and at WUE as well, since evaporative cooling trades water for power.

How often should PUE be measured?

Meter continuously, review monthly and report the annual figure. Monthly values show the effect of the seasons; the annual value is the one to compare and to report.

What is the difference between PUE and DCiE?

They are the same information. DCiE is the inverse of PUE as a percentage: PUE 1.25 equals DCiE 80 %.

Sources

Sources

  • ISO/IEC 30134-2:2016, Key performance indicators: Power usage effectiveness (PUE).
  • The Green Grid, PUE: A comprehensive examination of the metric (White Paper 49).
  • Uptime Institute, Global Data Center Survey 2025.
  • Commission Delegated Regulation (EU) 2024/1364; German Energy Efficiency Act (EnEfG), § 11.